Since the repair of the microwave tower grounding system, MGIO and Duffek have implemented a yearly check of the ground impedance. The specification it needs to meet is 25 ohms or less. Currently we are seeing after a year of service a total of 1 ohm which is only a .5 ohm increase since the fix. This is well within the Motorola standard.